VFD500 high performance vector control frequency inverter user manual Chapter 5 function code table
Zero speed detection
amplitude
Zero current detection level
0.0%~100.0% rated motor current
Zero current detection
delay time
0.000~30.000s
0.000~30.000s
Notice:When output current≤P08.10 and
endure P08.11 time,corresponding DO output
effective signal
Output overcurrent
threshold
0.0%~300.0%
motor rated time
Overcurrent detection
delay time
0.000~30.000sNotice:When output
current≥P08.12 and endure P08.13
time,corresponding DO output effective signal
When the output current ≤ zero current detection level, lasts for longer than zero current detection delay time,
DO terminal outputs ON signal.
!
When the output frequency reaches positive or negative detection amplitude of frequency detection value,
DO outputs ON signal. VFD500 series inverter provides two parameters of any arrival frequency detection
value, used to set frequency value and frequency detection range.
!