Chapter 5 Function code VFD500 high performance vector control frequency inverter user manual
P13.15
ACR Proportional Gain2
11000
0.5
P13.16
ACR Integral Time2
0.01300.00ms
10.00ms
ACRAutomatic current regulator.
ACR parameters adjust the PI adjustment parameter of the current loop which affects the dynamic response
speed and control accuracy directly. Generally, users do not need to change the default value;
Only apply to the vector control mode without PG card (P00.04=0).
P13.17
Voltage feedforward Gain
0100improve the dynamic response of vector
control,
0
P13.19
Voltage margin
0.0%50.0%improve the dynamic response of
weak magnetic curvature.
5.0%
P13.20
Flux weakening adjuster
integral time
0.001s-5.000s
0.010s
P13.22
Slip compensation
50%-200%
For sensorless vector control, this parameter is
used to adjust the speed stabilizing precision of
the motor.
When the speed is too low due to heavy load of
motor, this parameter needs to be enlarged, vice
versa.
100%
P13.23
SVC zero speed directives
0:No action 1:Output DC current
0
76