Chapter 5 Function code VFD500 high performance vector control frequency inverter user manual
P23.25
Fault source for auto reset
Define as per bit:#
bit0-overcurrent during acceleration;bit1-
overcurrent during deceleration#
bit2-overcurrent during constant speed;bit3-over
voltage during acceleration#
bit4-overvoltage during deceleratoin;bit5-
overvoltage during #
bit6-inverter undervoltage;bit7-input phase loss#
bit8-inverter overload;bit9-inverter overheat#
bit10-motor overload;bit11-motor overheat#
bit12-user’fault 1;bit13-user’fault 2#
bit14-Reserved;bit15-Reserved
0
P23.26
Fault auto Reset times
099
0
P23.27
Numberic output Action at
fault reset
0:Disabled#
1:Enabled
0
P23.28
Interval time of fault auto
reset
0.1s300.0s
0.5s
P23.29
Fault auto reset times
clearing time
0.1s3600.0s
10.0s
P23.30
Continuing Running
frequency selection when
trip
0Run at current frequency #
1Run at setted frequency#
2Run at upper limite frequency#
3Run at lower limit frequency#
4Run at abnormal back-up frequency
0
P23.31
Abnormal back-up
frequency
0.0%100.0%(maximum frequency )
5.0%
24 Group motor Protection parameter
P24.00
Motor overload protection
gain
0.2010.00
The larger the value, the longer the allowable
overload operation, and the higher the risk of
motor overheating damage.
1.00
P24.01
Motor overload starting
current at zero speed
50.0%150.0%
100.0%
P24.02
Motor overload starting
current at Rated speed
50.0%150.0%
115.0%
88

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VFD500 Series and is the answer not in the manual?

Danfoss VFD500 Series Specifications

General IconGeneral
BrandDanfoss
ModelVFD500 Series
CategoryDC Drives
LanguageEnglish

Related product manuals