VLT
®
5000 FLUX
Programming
361 Max Tracking Error
(MAX TRACKING ERR)
Value:
000 - 999 rpm
OFF (0 rpm)
Function:
Parameter 361 measures the deviation between
reference speed (calculated speed) and actual
mechanical shaft speed from feedback device
(incremental encoder).
Exceeding the value of parameter 361 will generate
Alarm 48 and cause a trip.
Description of choice:
Set the desired value. 0 speed will switch
off the function.
362 KTY Sensor Type
(KTY TYPE)
Value:
KTY Sensor 1 (KTY1)
[0]
KTY Sensor 2 (KTY2)
[1]
KTY Sensor 3 (KTY3)
[2]
Function:
Choice of the KTY sensor for temperature
compensation.
Description of choice:
The KTY sensor must be selected and enabled in
parameter 311 (Terminal 54, Analog input).
KTY Sensor 1 selected: 1 k
@100°C
KTY Sensor 2 selected: 1 k
@25°C
KTY Sensor 3 selected: 1 k
@25°C
NB!:
This parameter can only be changed, when
the motor is stopped.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
101

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 FLUX and is the answer not in the manual?

Danfoss VLT 5000 FLUX Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 FLUX
CategoryDC Drives
LanguageEnglish

Related product manuals