VLT
®
5000 FLUX
Miscellaneous
■ Status messages
Status messages appear in the 4th line of the display,
see the below example. The status message will
be on the display for approx. 3 seconds.
20.0Hz
SLOW DOWN
FREQUENCY
Start clockwise/anti-clockwise
(REM. START FORW./REV):
Input on digital inputs and parameter data are in conflict.
(MIXED START FORW./REV):
Input on digital inputs and parameter data are in conflict.
Slow-down (REM. SLOW DOWN):
The output frequency of the frequency converter
is reduced by the percentage value chosen
in parameter 219.
Catch-up (REM. CATCH UP):
The output frequency of the frequency converter
is increased by the percentage value chosen
in parameter 219.
Output speed high (REM. SPEED HIGH):
Theoutputfrequencyishigherthanthevalueset
in parameter 226. This message is only shown
when the motor is running.
Output speed high (LOCAL SPEED HIGH):
Theoutputfrequencyishigherthanthevalueset
in parameter 226. This message is only shown
when the motor is running.
Output speed high (MIXED SPEED HIGH):
Theoutputfrequencyishigherthanthevalueset
in parameter 226. This message is only shown
when the motor is running.
Output speed low (REM. SPEED LOW):
The output frequency is lower than the value set
in parameter 225. This message is only shown
when the motor is running.
Output speed low (LOCAL SPEED LOW):
The output frequency is lower than the value set
in parameter 225. This message is only shown
when the motor is running.
Output speed low (MIXED SPEED LOW):
The output frequency is lower than the value set
in parameter 225. This message is only shown
when the motor is running.
Output current high (REM. CURRENT HIGH):
The output current is higher than the value set
in parameter 224. This message is only shown
when the motor is running.
Output current high (LOCAL CURRENT HIGH):
The output current is higher than the value set
in parameter 224. This message is only shown
when the motor is running.
Output current high (MIXED CURRENT HIGH):
The output current is higher than the value set
in parameter 224. This message is only shown
when the motor is running.
Output current low (REM. CURRENT LOW):
The output current is lower than the value set
in parameter 223. This message is only shown
when the motor is running.
Output current low (LOCAL CURRENT LOW):
The output current is lower than the value set
in parameter 223. This message is only shown
when the motor is running.
Output current low (MIXED CURRENT LOW):
The output current is lower than the value set
in parameter 223. This message is only shown
when the motor is running.
Braking max. (REM. BRAKING MAX):
The brake is functioning.
Optimum braking is effected when the value in
parameter 402 Braking power limit, K W is exceeded.
Braking max. (LOCAL BRAKING MAX):
The brake is functioning.
Optimum braking is effected when the value in
parameter 402 Braking power limit, K W is exceeded.
Braking max. (MIXED BRAKING MAX):
The brake is functioning.
Optimum braking is effected when the value in
parameter 402 Braking power limit, K W is exceeded.
Braking (REM. BRAKING):
The brake is functioning.
Braking (LOCAL BRAKING):
The brake is functioning.
Braking (MIXED BRAKING):
MG.55.A6.02 - VLT is a registered Danfoss trademark
121