VLT
®
5000 FLUX
209 Ramp-up time 2
(RAMPUPTIME2)
Value:
0.00 - 3600 sec. (closed loop)
0.05 - 3600 sec. (open loop)
depends on unit
Function:
See description of parameter 207. Please note, that
the value 0.00 corresponds to 0.01 during speed.
Description of choice:
Set the desired ramp-up time.
Switching to ramp 2 may be activated via a signal
on digital input terminal 16, 17, 29, 32 or 33.
Ramp 1 will then be disabled.
210 Ramp-down time 2
(RAMPDOWNTIME2)
Value:
0.00 - 3600 sec. (closed loop)
0.05 - 3600 sec. (open loop)
depends on unit
Function:
See description of parameter 208. Please note, that
the value 0.00 corresponds to 0.01 during speed.
Description of choice:
Set the desired ramp-down time.
Switching to ramp 2 is effected via a signal
on digital input terminal 16, 17, 29, 32 or 33.
Ramp 1 will then be disabled.
211 Jog ramp time (JOG RAMP TIME)
Value:
0.00 - 3600 sec. (closed loop)
0.05 - 3600 sec. (open loop)
depends on unit
Function:
The jog ramp time is the acceleration/deceleration
time from 0 rpm to the rated motor frequency n
M,N
(parameter 104). It is assumed that the output current
is not higher than the torque limit (set in parameter 221).
The jog ramp time starts when a jog signal is
given via the control panel, the digital inputs or
the serial communication port.
Description of choice:
Set the desired ramp time.
212 Quick stop ramp-down time
(Q STOP RAMP TIME)
Value:
0.00 - 3600 sec. (closed loop)
0.05 - 3600 sec. (open loop)
depends on unit
Function:
The ramp-down time is the deceleration time from the
rated motor speed to 0 rpm, provided no over- voltage
arises in the inverter because of generating operation of
the motor or if the generated current becomes higher
than the torque limit (set in Parameter 222).
Quick-stop is activated by means of a signal
on digital input terminal 27 [2], or via the serial
communication port.
Description of choice:
Program the desired ramp-down time.
213 Jog speed
(JOG SPEED)
Value:
0.0 - Parameter 202
200 rpm
Function:
The jog speed n
JOG
is a fixed output speed at
which the frequency converter is running when
the jog function is activated.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
82