VLT
®
5000 FLUX
Programming
2048 pulses /rev. (2048)
[2048]
4096 pulses /rev. (4096)
[4096]
This value can also be set between 500 - 10.000 ppr.
The number of pulses per revolution can be
set between 500 - 10.000 ppr.
Function:
Set the encoder pulses per revolution on
the motor shaft.
This parameter is disabled in Open loop function.
(Parameter 100 = SPEED OPEN LOOP)
Description of choice:
Read the correct value from the encoder. Pay attention
to the speed limitation (rpm) for a given number of
pulses/rpm, see the drawing below:
The encoder used is a quadruple 5 volt type.
Max input frequency: 250 kHz.
See sections Feedback Systems, General Technical
Data and Control Board Encoder.
341 Terminal 46, digital output
(DO 46 FUNCTION)
Value:
See table in section Digital and relay outputs.
Function:
The output shifts from 0 V to 24 V when
the output is true.
Description of choice:
See description in section Digital relay outputs.
342 Terminal 46, output, pulse scaling
(DO 46 MAX PULS)
Value:
1 - 50000 Hz
5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value.
350 Encoder monitoring
(ENCODER MONITOR)
Value:
0 (OFF)
[0]
1 (OPTION & STANDARD)
[1]
Function:
If failure on encoder lines occur selection of this
parameter can generate an alarm (alarm 44) for
avoiding unintended start of the motor.
Encoder feedback pulse/rev function is disabled in
open loop (parameter 100 = Speed open Loop).
Description of choice:
Select ON when the encoder cables must
be supervised.
351 Encoder direction
(ENCODER DIR.)
Value:
0 (NORMAL CW)
[0]
1 (INVERSE CCW)
[1]
Function:
Change the detected encoder direction (revolution)
without changing the wires to the encoder.
Encoder monitoring function is disabled in open loop
(parameter 100 = Speed open loop).
Description of choice:
Select NORMAL CW when A channel is 90° (electrical
degrees) before channel B by clockwise rotation of
the encoder shaft. Select INVER SE CC W when A
channel is 90° (electrical degrees) after channel B by
counter clockwise rotation of the encoder shaft.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
99

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 FLUX and is the answer not in the manual?

Danfoss VLT 5000 FLUX Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 FLUX
CategoryDC Drives
LanguageEnglish

Related product manuals