470 Adaptive Gain Scale
(ADAPTIVE GAIN)
Value:
20%-500%
100%
Function:
In many applications there is a need for having a
different tuning of the speed controller depending on
motor-speed; a high gain at low speeds (precise) and
a lower gain at high speed (smooth). This Parameter
defines a scaling of the proportional gain of the
speed controller (Par. 417) at low speed..
471 Adaptive Gain Min. Speed
(AG MIN SPEED)
Value:
0-1500 RPM
50 RPM
Function:
In many applications there is a need for having a
different turning of the speed controller depending on
motor-speed; a high gain at low speeds (precise) and
a lower gain at high speed (smooth). This Parameter
defines the minimum speed of the speed range
where adaptive gain scale is faded towards 100%
of the value entered in Parameter 417.
472 Adaptive Gain Max. Speed
(AG MAX SPEED)
Value:
0-1500 RPM
50 RPM
Function:
In many applications there is a need for having a
different tuning of the speed controller depending on
motor-speed; a high gain at low speeds (precise) and
a lower gain at high speed (smooth). This Parameter
defines the maximum speed of the speed range
where adaptive gain scale is faded towards 100%
of the value entered in Parameter 417.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
108

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 FLUX and is the answer not in the manual?

Danfoss VLT 5000 FLUX Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 FLUX
CategoryDC Drives
LanguageEnglish

Related product manuals