VLT
®
5000 FLUX
Programming
■ Serial communication
■ Introduction
The purpose of the serial communication parameters is to select and adjust parameters in conjunction with
RS 485 field bus. See wiring diagram ’Bus connection’ in the installation section.
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
500 Address 1 1 - 126 Yes No 0 6
501 Baudrate 9600 Baud Yes No 0 5
502 Coasting Logic or Yes Yes 0 5
503 Quick-stop Logic or Yes Yes 0 5
504 DC-brake Logic or Yes Yes 0 5
505 Start Logic or Yes Yes 0 5
506 Reversing Digital input Yes Yes 0 5
507 Selection of setup Logic or Yes Yes 0 5
508 Selection of speed Logic or Yes Yes 0 5
509 Bus jog 1 200 rpm 0.0 - parameter 202 Yes Yes -1 6
510 Bus jog 2 200 rpm 0.0 - parameter 202 Yes Yes -1 6
512 Telegram profile FC Drive No Yes 0 5
513 Bus time interval 1 sec. 1 - 99 s Yes Yes 0 5
514 Bus time interval function Off Yes Yes 0 5
515 Data read-out: Reference % No No -1 3
516 Data read-out: Reference unit No No -3 4
518 Data read-out: Frequency No No -1 6
520 Data read-out: Current No No -2 7
521 Data read-out: Torque No No -1 3
522 Data read-out: Power, kW No No -1 7
523 Data read-out: Power, HP No No -2 7
524 Data read-out: Motor voltage No No -1 6
525 Data read-out: DC link voltage No No 0 6
526 Data read-out: Motor temp. No No 0 5
527 Data read-out: VLT temp. No No 0 5
528 Data read-out: Digital input No No 0 5
529 Data read-out: Terminal 53,
analog input
No No -2 3
530 Data read-out: Terminal 54,
analog input
No No -2 3
531 Data read-out: Terminal 60,
analog input
No No -5 3
532 Data read-out: Pulse reference No No -1 7
533 Data read-out: External reference % No No -1 3
534 Data read-out: Status word, binary No No 0 6
535 Data read-out: Brake power/2 min. No No 2 6
536 Data read-out: Brake power/sec. No No 2 6
537 Data read-out: Heat sink temperature No No 0 5
538 Data read-out: Alarm word, binary No No 0 7
539 Data read-out: VLT control word, binary No No 0 6
540 Data read-out: Warning word, 1 No No 0 7
541 Data read-out: Extended status word No No 0 7
557 Data read-out: Motor RPM No No 0 4
558 Data read-out: Motor RPM x scaling No No -2 4
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark