VLT
®
5000 FLUX
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5062 5072 5102
Normal overload torque (110 %):
Output current I
VLT,N
[A] (380-440 V) 106 147 177
I
VLT, MAX
(60 s) [A] (380-440 V) 117 162 195
I
VLT,N
[A] (441-500 V) 106 130 160
I
VLT, MAX
(60 s) [A] (441-500 V) 117 143 176
Output S
VLT,N
[kVA] (380-440 V) 80.8 102 123
S
VLT,N
[kVA] (441-500 V) 91.8 113 139
Typical shaft output P
VLT,N
[kW] (400 V) 55 75 90
P
VLT,N
[HP] (460 V) 75 100 125
P
VLT,N
[kW] (500 V) 75 90 110
High overload torque (160 %):
Output current I
VLT,N
[A] (380-440 V) 90 106 147
I
VLT, MAX
(60 s) [A] (380-440 V) 135 159 221
I
VLT,N
[A] (441-500 V) 80 106 130
I
VLT, MAX
(60 s) [A] (441-500 V) 120 159 195
Output S
VLT,N
[kVA] (380-440 V) 68.6 73.0 102
S
VLT,N
[kVA] (441-500 V) 69.3 92.0 113
Typical shaft output P
VLT,N
[kW] (400 V) 45 55 75
P
VLT,N
[HP] (460 V) 60 75 100
P
VLT,N
[kW] (500 V) 55 75 90
Max. cable cross-section to motor, IP 54 50/0
5)
150/300
mcm
6)
150/300
mcm
6)
brake and loadsharing [mm
2
]/[AWG]
2)
IP20 50/0
5)
120/250
mcm
5)
120/250
mcm
5)
Min. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
4)
16/6 25/4 25/4
Rated input current I
L,N
[A] (380 V) 104 145 174
I
L,N
[A] (460 V) 104 128 158
Max. cable cross-section IP 54 50/0
5)
150/300
mcm
150/300
mcm
power[mm
2
]/[AWG]
2)
IP 20 50/0
5)
120/250
mcm
5)
120/250
mcm
5)
Max. pre-fuses [-]/UL
1)
[A] 160/150 225/225 250/250
Efficiency
3)
>0.97 >0.97 >0.97
Weight IP 20 EB [kg] 43 54 54
Weight IP 54 [kg] 60 77 77
Power loss at max. load.
- high overload torque (160 %) [W] 1122 1058 1467
- normal overload torque (110 %) [W] 1322 1467 1766
Enclosure
IP20/
IP 54
IP20/
IP 54
IP20/
IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply with national and
local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
used.
6. Brake and loadsharing: 95 mm
2
/AWG3/0
MG.55.A6.02 - VLT is a registered Danfoss trademark
150