Model
525–550 V
551–690 V
N250
8246
6454
6454
5199
N315
10308
8246
8246
6454
N355
10308
10308
10308
8246
N400
7768
6872
6872
5498
N500
10995
6872
7768
6872
N560
9919
9919
8605
7768
N630
10995
9919
9919
8605
N710
13744
10995
10995
9919
N800
13744
13744
13744
10995
11.6.6 dU/dt Filter Losses
Table 152: Power Losses for dU/dt Filter Option, 380–480 V (Losses Shown in Watts)
Model
380–440 V
441–480 V
NO
HO
NO
HO
N110
350
244
281
199
N132
526
350
448
281
N160
327
223
300
190
N200
514
327
429
300
N250
834
565
710
472
N315
1251
834
1036
710
N355
713
593
573
480
N400
914
713
757
573
N450
1054
795
878
757
N500
1402
1158
1101
964
N560
1774
1402
1434
1101
Table 153: Power Losses for dU/dt Filter Option, 525–690 V (Losses Shown in Watts)
Model
525–550 V
551–690 V
NO
HO
NO
HO
N110
453
308
414
281
N132
204
146
187
134
N160
314
204
287
187
N200
498
314
456
287
N250
302
211
277
193
AQ262141056213en-000201 / 130R0882 | 183Danfoss A/S © 2020.09