EasyManua.ls Logo

Danfoss VLT FC 103 - 4.7 Cooling Requirements

Danfoss VLT FC 103
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
On power-up, the FC 103 launches an application guide. In
the event of power failure, the application guide is
accessed through the Quick Menu screen.
130BC951.10
Figure 3.1 Quick Menu Screen
If [Cancel] is pressed, the FC 103 will return to the status
screen. An automatic timer will cancel the wizard after five
minutes of inactivity (no keys pressed). The wizard must be
re-entered through the Quick Menu as described below.
If [OK] is pressed, the Application Guide will start with the
following screen:
130BC952.10
Figure 3.2 Start-up of Application Guide
NOTICE!
Numbering of steps in the wizard (e.g., 1/12) can change
depending on workflow choices.
This screen will automatically change to the first input
screen of the Application Guide:
130BC953.10
Figure 3.3 Language Selection
130BC954.10
Figure 3.4 Application Selection
Compressor pack set-up
The following example shows screens for a compressor
pack set-up:
Figure 3.5 Voltage and Frequency Set-up
Figure 3.6 Current and Nominal Speed Set-up
Figure 3.7 Min. and Max. Frequency Set-up
Start-up and Functional Tes... Instruction Manual
MG16E222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 33
3 3

Table of Contents

Other manuals for Danfoss VLT FC 103

Related product manuals