Enclosure size Power [kW (hp)] Non-UL fuse Non-UL circuit breaker UL fuse
K1
0.37 (0.5)
gG-10
PKZM0-16
JJS-3
0.55–0.75
(0.74–1.0)
JJS-6
1.1–1.5
(1.48–2.0)
gG-20
JJS-10
2.2 (3.0) JJS-15
K2
3.0–5.5
(4.0–7.5)
gG-25 PKZM0-20 JJS-25
K3
7.5
(10)
gG-25 PKZM0-25 JJS-25
K4
11–15
(15–20)
gG-50 – JJS-50
K5
18.5–22
(25–30)
gG-80 – JJS-80
Table 7.4 Fuse and Circuit Breaker, 380–480 V
7.9 Eciency
Eciency of the frequency converter (η
VLT
)
The load on the frequency converter has little eect on its
eciency. In general, the eciency is the same at the
rated motor frequency f
M,N
. This rule also applies even if
the motor supplies 100% of the rated shaft torque or only
75%, for example if there is part loads.
This also means that the eciency of the frequency
converter does not change even if other U/f characteristics
are selected.
However, the U/f characteristics inuence the eciency of
the motor.
The eciency declines a little when the switching
frequency is set to a value above the default value. If the
mains voltage is 480 V, or if the motor cable is longer than
30 m (98.4 ft), the eciency is also slightly reduced.
Frequency converter eciency calculation
Calculate the eciency of the frequency converter at
dierent loads based on Illustration 7.2. Multiply the factor
in Illustration 7.2 by the specic eciency factor listed in
the specication tables in chapter 7.1 Power-dependent
Specications:
1.0
0.99
0.98
0.97
0.96
0.95
0.93
0.92
0% 50% 100% 200%
0.94
Relative Eciency
130BB252.11
1.01
150%
% Speed
100% load 75% load 50% load 25% load
Illustration 7.2 Typical Eciency Curves
Eciency of the motor (η
MOTOR
)
The eciency of a motor connected to the frequency
converter depends on the magnetizing level. In general,
the eciency is as good as with mains operation. The
eciency of the motor depends on the type of motor.
In the range of 75–100% of the rated torque, the eciency
of the motor is practically constant, both when controlled
by the frequency converter and when running directly on
mains.
In small motors, the inuence from the U/f characteristic
on eciency is marginal. However, in motors from 11 kW
(14.8 hp) and up, the advantages are signicant.
In general, the switching frequency does not aect the
eciency of small motors. Motors from 11 kW (14.8 hp)
and up have their eciency improved 1–2% because the
sine shape of the motor current is almost perfect at high
switching frequency.
Eciency of the system (η
SYSTEM
)
To calculate the system eciency, the eciency of the
frequency converter (η
VLT
) is multiplied by the eciency of
the motor (η
MOTOR
):
η
SYSTEM
= η
VLT
x η
MOTOR
Specications
VLT
®
Midi Drive FC 280
82 Danfoss A/S © 03/2016 All rights reserved. MG07B102
77