ICON and No:
DESCRIPTION
ADJUSTMENT LIMITS
Factory
Set
E.50
PID I VALUE :
PID control I gain
%0.0 ... 99.9
% 0
E.51
PID D VALUE :
PID control D gain
%0.0 ... 99.9
% 5.0
E.52
PID I INVRS VAL :
PID control inverse I
gain
%0.0 ... 99.9
% 0
E.53
PID CNTRL DELAY :
PID control activation
delay
1 ... 999 sec
Please see chapter 6.9 for details.
10 sec
E.54
PID START TEMP. :
PID control start
temperature
0 ... (E.08-2)
Please see chapter 6.9 for details.
15 °C
E.55
MAX SLAVES :
Maximum number of
slaves under load
0 ... 8
0
E.56
DRYER DLY.TIMER :
Dryer function delay
timer
0 ... 999 sec
If this parameter is set to 0 then the dryer
function is disabled.
Please see chapter 6.7 for details.
0 sec