DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006 17
6.2 LCD DISPLAY AREAS
Instrument Values
Units of Measure
Display Information &
Alarm Icons
User Definable Alarms/Indicators
NOTE:- The Engine Hours Run counter will only display the accumulated hours to the
nearest 12 Minutes (0.2Hr). The accumulated time will be recorded in HH: MM however.
CAUTION!:-If the DC supply to the module is interrupted the hours run counter will not
remember any ‘un-displayed’ minutes accumulated since the last 12 Minute display update.
i.e.
10 Hours 38 Minutes accumulated before DC supply is removed…
(10.6 Hours displayed)
would become …10 Hours 36Minutes on restoration of DC supply.
(10.6 Hours still displayed)
This will only occur in the event of a total DC supply break and will NOT occur if the module is
simply switched to the Stop/Reset position.