DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006 33
11 ELECTRICAL CONNECTIONS
Connections to the Module are via plug and sockets.
11.1 CONNECTION DETAILS
The following describes the connections and recommended cable sizes to the 7 plugs and sockets on the rear
of the Module. See rear panel layout FIG 6.
11.1.1 PLUG “A” 8 WAY
PIN No DESCRIPTION CABLE SIZE NOTES
1 DC Plant Supply Input
(Negative)
2.5mm² (13 AWG)
2 DC Plant Supply Input
(Positive)
2.5mm² (13 AWG) (Recommended Maximum Fuse 21A)
3 Emergency Stop Input 2.5mm (13 AWG) Plant Supply Positive. Also supplies fuel & start
outputs.
(Recommended Maximum Fuse 32A)
4 Fuel relay Output 2.5mm² (13 AWG) Plant Supply Positive from pin 3. 16 Amp rated.
5 Start relay Output 2.5mm² (13 AWG) Plant Supply Positive from pin 3. 16 Amp rated.
6 Auxiliary Output relay 1 1.0mm² (18 AWG) Plant Supply Positive. 5 Amp rated.
7 Auxiliary Output relay 2 1.0mm (18 AWG) Plant Supply Positive. 5 Amp rated.
8 Auxiliary Output relay 3 1.0mm (18 AWG) Plant Supply Positive. 5 Amp rated.
11.1.2 PLUG “B” 11 WAY
PIN No DESCRIPTION CABLE SIZE NOTES
9 Charge fail / excite 2.5mm² (13 AWG) Do not connect to ground (battery Negative)
10 Auxiliary input 1 0.5mm² (20 AWG) Switch to Negative
11 Auxiliary input 2 0.5mm² (20 AWG) Switch to Negative
12 Auxiliary input 3 0.5mm² (20 AWG) Switch to Negative
13 Auxiliary input 4 0.5mm² (20 AWG) Switch to Negative
14 Auxiliary input 5 0.5mm² (20 AWG) Switch to Negative
15 Not connected -
16 Functional Earth 2.5mm² (13 AWG) Connect to a good clean earth point
17 Magnetic pickup
Positive
0.5mm² (20 AWG) Connect to Magnetic Pickup device
18 Magnetic pickup
Negative
0.5mm² (20 AWG) Connect to Magnetic Pickup device
19 Not connected -
NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.
NOTE:- Terminal numbers 20-34 are not fitted to the 5110 controller
11.1.3 PLUG “F” 4 WAY
PIN No DESCRIPTION CABLE SIZE NOTES
35 Generator L1 voltage monitoring
input
1.0mm² (18 AWG) Connect to generator L1 output (AC)
(Recommend 2A fuse)
36 Generator L2 voltage monitoring
input
1.0mm² (18 AWG) Connect to generator L2 output (AC)
(Recommend 2A fuse)
37 Generator L3 voltage monitoring
input
1.0mm² (18 AWG) Connect to generator L3 output (AC)
(Recommend 2A fuse)
38 Generator Neutral input 1.0mm² (18 AWG) Connect to generator Neutral terminal
(AC)
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deep Sea Electronics Plc DSE5110 and is the answer not in the manual?

Deep Sea Electronics Plc DSE5110 Specifications

General IconGeneral
BrandDeep Sea Electronics Plc
ModelDSE5110
CategoryControl Unit
LanguageEnglish

Related product manuals