Edit Configuration - Module
10
Miscellaneous
Options
All Warnings Are
Latched
= Normal Operation, the warnings and pre-alarms will automatically reset once the
triggering condition has cleared.
= Warnings and pre-alarms latch when triggered. Resetting the alarm is performed by
either an external reset applied to one of the inputs or, the ‘Stop/Reset’ pushbutton must be
operated (once the triggering condition has been cleared).
Enable Alternative
Breaker Button
Control
Not DSE7410
Default breaker button control is transfer to Generator/ Transfer to mains:
Alternative breaker button control is:-
Open Mains breaker / Close mains breaker
Open Generator breaker / Close breaker.
Enable sleep mode
=Normal operation
=The module goes into "sleep mode” if left in manual mode for a prolonged time with no
button presses.
Enable manual fuel
pump control
=Normal operation
=Allows manual fuel pump control when the “fuel level” instrument page is being viewed.
Support right-left
languages in
module strings
Determines the direction of text input where supported (i.e. configurable input text)
=left to right language support
=right to left language support