4.9.6 CRANKING
Crank disconnect settings are used to detect when the set fires during the starting sequence.
As the set is cranked, the first parameter that passes it’s crank disconnect setting will result in the cessation of
the cranking signal.
Having more than one crank disconnect source allows for a much faster crank disconnect response leading to
less wear on the engine and starter components, and provides added safety in case one source is lost, by a
blown or tripped fuse for example.
Click and drag to
change the setting.
Type the value
or click the up
and down
arrows to
change the
settings
If
check oil pressure prior to
starting is enabled, the cranking
will not be allowed if the oil
pressure is not seen as being
low. This used as a double check
that the engine is stopped before
the starter is engaged
When enabled, releasing the start button
during a manual start will also disconnect
the crank.
Manual Crank Limit is provided to protect
the engine from being cranked too long in
case of a start failure.