4.6 TIMERS
Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the same
page as the alarm setting. Timers not associated with an alarm are located on the timers page.
The Timers page is subdivided into smaller sections. Select the required section with the mouse.
4.6.1 START TIMERS
Timer
Description
Remote Start Off Load
Used to give a delay before starting in AUTO mode. This timer is activated upon the respective
start command being issued.
Typically this timer is applied to prevent starting upon fleeting remote start signals or short term
mains failures.
Remote Start On Load
Mains fail
Telemetry Start
Mains Transient Delay
Used to delay the detection of mains failure. This is normally used to prevent short term
transients or brownout conditions from being classified as a Mains Failure and opening the
breaker.
Parameters detailed overleaf...
Click and drag to change the setting.
Timers increment in steps of 1 second up to
one minute, then in steps of 30 seconds up
to 30 minutes, then in steps of 30 minutes
thereafter (where allowed by the limits of the
timer).