Edit Configuration - Module
9
4.2.1 MODULE OPTIONS
Miscellaneous
Options
Enable fast loading
feature
= Normal Operation, the safety on timer will be observed in full. This feature is useful if the
module is to be used with some small engines where pre-mature termination of the delay
timer can lead to overspeed alarms on start up.
= The module will terminate the safety on timer once all monitored parameters have
reached their normal settings. This feature is useful if the module is to be used as a standby
controller as it allows the generator to start and go on load in the shortest possible time.
NOTE: - Enabling Fast Loading is only recommended where steps have been
taken to ensure rapid start up of the engine is possible. (For example when fitted with
engine heaters, electronic governors etc.)
Audible alarm prior
to starting
= The module will start with no audible indication
= The module will give an audible warning during the pre-heat timer as an indicator that
the set is about to run. This is often a site’s specification requirement of AUTO mode
operation.