Table 4.41 Default parameters
Parameter Range Default
Set point 70 to 250 % 200 %
Delay 0 s to 1 h 0.3 s
Enable Not enabled, Enabled Not enabled
Latch Not enabled, Enabled Enabled
Action Trip bus tie breaker
Inhibit Bus tie breaker open
DESIGNER'S HANDBOOK 4189340911K UK Page 138 of 521