3.4.7 Over-current (ANSI 50TD)
Protection IEC symbol (IEC60617) ANSI (IEEE C37.2) IEC 61850 Operate time
Over-current 3I>, 3I>> 50TD PTOC < 100 ms
The alarm response is based on the highest phase current true RMS values from the source,
as measured by the controller.
Configure the parameters under Configure > Parameters > [Source] > Current protections > Over-current #, where # is 1 or 2.
Table 3.35
Default parameters
Parameter Range Over-current 1 Over-current 2
Set point Variable. Depends on current transformer settings. 100 % 110 %
Delay 0.00 s to 1 h 20 s 60 s
Enable Not enabled, Enabled Enabled Enabled
Latch Not enabled, Enabled Not enabled Enabled
Alarm action Warning Trip [Breaker]
3.4.8 Fast over-current (ANSI 50/50TD)
Protection
IEC symbol (IEC60617) ANSI (IEEE C37.2) IEC 61850 Operate time
Fast over-current 3I>>> 50/50TD* PIOC* < 50 ms
*Note: ANSI 50 and IEC 61850-5 PIOC apply when the Delay parameter is 0 s.
The alarm response is based on the highest phase current true RMS values from the source,
as measured by the controller.
Configure the parameters under Configure > Parameters > [Source] > Current protections > Fast over-current #, where # is 1
or 2.
Table 3.36
Default parameters
Parameter Range Fast over-current 1 Fast over-current 2
Set point Variable. Depends on current transformer settings. 200 % 300 %
Delay 0.00 s to 1 h 0.00 s 0.00 s
Enable Not enabled, Enabled Not enabled Not enabled