Parameters
Configure the parameters under Configure > Parameters > Local > 4th current input > Neutral inverse time over-current.
Table 3.65 Default parameters
Parameter Range
Neutral inverse time
over-current
Curve See the reference IEC Inverse
Limit (the set point, also known as LIM) 2 to 200 % of nominal current (4th current input) 30 %
Time multiplier setting (TMS) 0.01 to 100.0 1.0
Threshold 1.0 to 1.3 1.1
k (only used if custom curve is selected) 0.001 s to 2 min 0.14 s
c (only used if custom curve is selected) 0 s to 1 min 0 s
alpha (α, or a) (only used if custom curve is
selected)
0.001 to 1 0.02
Enable Not enabled, Enabled Enabled
Latch Not enabled, Enabled Enabled
Alarm action Trip [Breaker]
More information
See Source AC protections, Inverse time over-current (ANSI 51) in this chapter for the calculation method, the
standard curves, and information about the definite time characteristic.
3.7 ACM voltage measurement errors
3.7.1 [Source]/[Busbar] L1-L2-L3 wire break
Controller types: GENSET, SHAFT generator, SHORE connection and BUS TIE breaker controllers
These alarms alert the operator to a voltage measurement failure:
[Source] L1-L2-L3 wire break
[Busbar] L1-L2-L3 wire break
The controller only activates the alarm when all of these conditions are met:
The generator breaker is closed
Voltage is detected by one set of ACM voltage measurements
No voltage is detected on all three phases for the other set of ACM voltage
measurements
0
1
Time
Busbar
L1-L2-L3
Wire break
L1 L2 L3
Generator
voltage
L1 L2 L3
Busbar
voltage
Parameters
Configure > Parameters > [Source] > AC setup > Multiple phase wire break
DESIGNER'S HANDBOOK 4189340911K UK Page 87 of 521