9.9.8 Emergency-main busbar maximum parallel time
This alarm is for the maximum time that the emergency genset may run in parallel to the main busbar.
The timer starts when the emergency genset is synchronised with the main busbar. The alarm action is Trip
tie breaker and the alarm is latched.
G
Emergency
load
Configure the parameters under Configure > Parameters > Local power management > Parallel timers > EDG max. parallel
time.
Table 9.15
Default parameters
Parameter Range Default
Delay 0.1 s to 1 h 30.0 s
Enable Not enabled, Enabled Enabled
INFO
This alarm is ONLY present in the EMERGENCY genset controller.
INFO
This alarm is disabled during the parallel test.
9.9.9 Other EMERGENCY genset controller alarms
The following alarms are included on both the GENSET and EMERGENCY genset controllers:
Emergency stop
Primary running feedback failure
Crank failure
Start failure
Engine start (external)
Voltage or frequency not OK
Stop failure
Engine stop (external)
Overspeed
Underspeed
Start enable removed during start
Total running hours notification
Trip running hours notification
EIM # relay 4 wire break*
Magnetic pickup wire break*
More information
For the alarms marked with *, see Hardware characteristics and configuration for more information.
For the other alarms, see GENSET controller, GENSET controller alarms for more information.