Table 8.36 Default parameters
Parameter Range Default
Enable Not enabled, Enabled Enabled
Latch Not enabled, Enabled Enabled
Action Block
8.7.12 Start enable removed during start
The alarm response is based on the engine start-up sequence. This alarm is activated if the engine start-up procedure is interrupted
by the loss of the Start enable input before the engine has started.
Configure the parameters under Configure > Parameters > Engine > Start sequence > Start enable remove during start.
Table 8.37
Default parameters
Parameter Range Default
Alarm action Warning
Enable Not enabled, Enabled Not enabled
8.7.13 Stop failure
This alarm is for genset stop failure.
The controller attempts to stop the genset by activating the Stop coil output (if present) or
alternatively, by deactivating the Run coil output (if present). If Running detection is still ON
after the delay time, the controller activates this alarm.
OFF
Running
detection
time
t
delay
ON
Configure the parameters under Configure > Parameters > Engine > Stop sequence > Stop failure.
Table 8.38
Default parameters
Parameter Range Default
Delay 0 s to 5 m 30 s
Enable Not enabled, Enabled Enabled
Action Warning
8.7.14 Engine started (external)
This alarm is to alert the operator to an externally-initiated engine start.
The alarm is activated if the controller did not initiate an engine start, but Running detection
shows that the engine is running.
On
Off
Running
detection
Time
Delay
DESIGNER'S HANDBOOK 4189340911K UK Page 316 of 521