Table 7.30 Default parameters
Parameter Range Default
Action Warning
7.9.6 Missing controller ID #
This alarm communicates a communication failure with one or more controllers in the single-line diagram.
The alarm is activated when a controller is present on the single-line diagram, but the controller displaying the alarm cannot
communicate with it.
The alarm is always enabled, the alarm action is Warning. The alarm also forces all the controllers in the section under switchboard
control. The alarm parameters are not visible.
7.9.7 Duplicate controller ID
Each controller is delivered with this default alarm to communicate that there is another controller with the same Controller ID in the
network.
The alarm is based on the network between the controllers included in the single-line diagram. The alarm is activated when the
controller detects another controller with the same Controller ID as itself. The affected controllers are also forced under switchboard
control.
Configure the parameters under Configure > Parameters > System > Monitoring > Duplicate controller ID. This alarm is always
enabled.
Table 7.31
Default parameters
Parameter Range Default
Action Warning
7.9.8 Missing any controller
This alarm informs the operator that there is a communication failure with one or more controllers.
The alarm is based on the network between the controllers included in the single-line diagram. The controller activates the alarm if
there is at least one controller in the single-line diagram that it cannot communicate with. This alarm is not suppressed by Missing all
controllers.
Configure the parameters under Configure > Parameters > System > Monitoring > Missing any controller. This alarm is always
enabled.
Table 7.32
Default parameters
Parameter Range Default
Action Warning
7.9.9 Missing controllers
This alarm informs the operator that there is a communication failure with one or more controllers. The alarm is based on the
network between the controllers included in the single-line diagram. The controller activates the alarm when the number of missing
controllers in the section reaches the set point. This alarm is not suppressed by Missing all controllers.
DESIGNER'S HANDBOOK 4189340911K UK Page 276 of 521