Configure the parameters under Configure > Parameters > Engine > Start sequence > Engine started (external).
Table 8.39 Default parameters
Parameter Range Default
Enable Not enabled, Enabled Enabled
Action Warning
8.7.15 Engine stopped (external)
This alarm alerts the operator to an externally-initiated engine stop.
The alarm is activated if the controller did not initiate an engine stop, but Running detection
shows that the engine has stopped.
On
Off
Running
detection
Time
Delay
Configure the parameters under Configure > Parameters > Engine > Stop sequence > Engine stopped (external).
Table 8.40
Default parameters
Parameter Range Default
Enable Not enabled, Enabled Enabled
Latch Not enabled, Enabled Enabled
Action Block
8.7.16 Total running hours notification
This alarm notifies the operator when the total running hours exceeds the set point.
The alarm response is based on the Total running hours counter.
Configure these parameters under Configure > Parameters > Engine > Maintenance > Running hours total.
Table 8.41
Default parameters
Parameter Range Running hours total
Set point 0 to 1,000,000 hours 500 hours
Enable Not enabled, Enabled Not enabled
Action Warning
DESIGNER'S HANDBOOK 4189340911K UK Page 317 of 521