Table 3.54 Default parameters
Parameter Range Busbar over-voltage 1 Busbar over-voltage 2
Set point 90 to 120 % of nominal voltage 105 % 115 %
Delay 0.00 s to 1 h 5.00 s 3.00 s
Enable Not enabled, Enabled Enabled Enabled
Latch Not enabled, Enabled Not enabled Enabled
Action Warning Trip [Breaker]*
*Note: For the EMERGENCY genset controller: This alarm action trips the tie breaker to the main busbar. For other controllers: The
controller trips the breaker to the equipment it controls.
Table 3.55
Default inhibits
Controller type Inhibit(s)
GENSET • Generator breaker open
EMERGENCY genset
• Generator breaker open
• Tie breaker open
• EDG handling blackout
SHAFT generator • Shaft breaker open
SHORE connection • Shore breaker open
3.5.2 [Busbar] under-voltage (ANSI 27)
Protection
IEC symbol (IEC60617) ANSI (IEEE C37.2) IEC 61850 Operate time
Under-voltage U<, U<< 27 PTUV < 50 ms
The alarm response is based on the lowest phase-to-phase voltage, or the lowest phase-to-
neutral voltage, from the busbar, as measured by the controller. For the BUS TIE breaker
controller, these voltages are measured on busbar B.
Configure the parameters under Configure > Parameters > [Busbar] > Voltage protections > Under-voltage #, where # is 1 or 2.
Table 3.56
Default parameters
Parameter Range Busbar under-voltage 1 Busbar under-voltage 2
Set point 50 to 100 % of nominal voltage 95 % 80 %
Delay 0.00 s to 1 h 5.00 s 3.00 s
Enable Not enabled, Enabled Enabled Enabled
Latch Not enabled, Enabled Not enabled Enabled
Action Warning Trip [Breaker]*
*Note: For the EMERGENCY genset controller, this alarm action trips the tie breaker to the main busbar. For other controllers: the
controller trips the breaker to the equipment it controls.
DESIGNER'S HANDBOOK 4189340911K UK Page 80 of 521