More information
See the Breakers, synchronisation and de-loading chapter for more information on synchronisation and breakers. This
includes the inputs and output functions and the parameters to configure.
For the SHORE connection controller, the breaker abbreviation ([*B]) is SCB. [Breaker] refers to Shore connection breaker.
11.3.2 Shore connection breaker close flowchart
The following flowchart shows the sequence that the controller normally uses to close the shore connection breaker.
More information
See SHORE connection controller, Shore connection breaker, Shore connection breaker blackout close flowchart
for information about how to allow the shore connection to connect to a dead busbar.
This flowchart does not apply to switchboard control. When the controller is under switchboard control, it will not close the breaker.
If, for example, the operator presses the push-button Close breaker on the display unit, the controller ignores this command.