EasyManua.ls Logo

Deif PPM 300 - 13.7 Input;Output Module IOM3.1; IOM3.1 Terminal Overview

Deif PPM 300
521 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Category Specification
ON: -36 to -8 V DC, and 8 to 36 V DC
OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 4.7 kΩ
Voltage withstand: ±36 V DC
Terminal connections
Relay outputs: Terminals: Standard 45° plug, 2.5 mm
2
Wiring: 0.5 to 2.5 mm
2
(22 to 12 AWG), multi-stranded
Digital inputs: Terminals: Standard 45° plug, 1.5 mm
2
Wiring: 0.5 to 1.5 mm
2
(28 to 16 AWG), multi-stranded
Torques and terminals
Module faceplate screws: 0.5 N·m (4.4 lb-in)
Connection of wiring to relay output terminals: 0.5 N·m (4.4 lb-in)
Connection of wiring to digital input terminals: 0.25 N·m (2.2 lb-in)
UL/cUL Listed: Wiring must be minimum 90 ºC (194 °F) copper conductors only.
Galvanic isolation
Between relay groups and other I/Os: 2210 V, 50 Hz for 60 s
Between digital input groups and other I/Os: 600 V, 50 Hz for 60 s
Ingress protection
Unmounted: No protection rating
Mounted in rack: IP20 according to IEC/EN 60529
Size L 28 mm × H 162 mm × D 150 mm (1.1 in × 6.4 in × 5.9 in)
Weight 196 g (0.4 lb)
13.7.2 IOM3.1 terminal overview
Terminal
Symbol Name Type
1 Normally open
Relay output (250 V AC or 30 V DC, and 6 A)
2 Common
3 Normally closed
4 Normally open
5 Common
6 Normally closed
7 Normally open
8 Common
9 Normally closed
10 Normally open
11 Common
12 Normally closed
DESIGNER'S HANDBOOK 4189340911K UK Page 438 of 521