Functions
Genset(s) drive the ship's shaft
Another shaft generator drives the ship's shaft
Power requirement to drive the ship's shaft treated as a load
Propeller zero pitch digital input
Shaft generator fixed speed digital input
Counters
Display unit counters, to edit or reset
Running hours (total, and trip)
Shaft generator breaker operations and trips
Energy export (active and reactive) (to the busbar)
Energy import (active and reactive) (to the shaft generator)
External breaker operations
Energy counters with configurable digital outputs (for external counters)
Energy export (active and reactive) (to the busbar)
Energy import (active and reactive) (to the shaft generator)
Control types
Power management system (PMS) control
Display unit push-buttons for breaker operations
Synchronisation, de-loading, and breaker control
Push-button functions also possible using inputs, PICUS, and/or Modbus
Switchboard control
Operator controls the system from the switchboard
Only the controller protections are active
Regulation
Regulators for relay outputs and analogue outputs
Regulation delay
Governor regulation
Fixed power
Active power load sharing
Active power ramp down
Frequency-dependent power droop
AVR regulation
Fixed cos phi
Fixed reactive power
Reactive power load sharing
Voltage droop
Configurable: Power ramp up, power ramp down
10.2 SHAFT generator controller principles
10.2.1 Adding a SHAFT generator controller to the single-line diagram
Configure each SHAFT generator controller in the single-line diagram, using PICUS.
To add a SHAFT generator controller to the single-line diagram:
1. In PICUS, under Configure > Single-line, drag the shaft generator icon to the right place on the
single-line diagram.
2. Select the SHAFT generator controller on the single-line diagram, and make sure that its Controller ID
is correct.
3. Broadcast the changes to all the controllers in the system.
If needed you can override the controller ready status.