3.4.3 [Source] under-voltage (ANSI 27)
Protection IEC symbol (IEC60617) ANSI (IEEE C37.2) IEC 61850 Operate time
Under-voltage U<, U<< 27 PTUV < 100 ms
The alarm response is based on the lowest phase-to-phase voltage, or the lowest phase-to-
neutral voltage, from the source, as measured by the controller. The phase-to-phase voltage is
the default.
Set
point
Value
time
Delay
Configure the parameters under Configure > Parameters > [Source] > Voltage protections > Under-voltage #, where # is 1 or 2.
Table 3.29
Default parameters
Parameter Range Under-voltage 1 Under-voltage 2
Set point 50 to 100 % of nominal voltage 95 % 80 %
Delay 0.00 s to 1 h 5.00 s 3.00 s
Enable Not enabled, Enabled Enabled Enabled
Latch Not enabled, Enabled Not enabled Enabled
Action Warning Block
Table 3.30 Default inhibits
Controller type Inhibit(s)
GENSET
Generator breaker closed
Engine not running
EMERGENCY genset
Engine not running
EDG in parallel
EDG handling blackout
SHAFT generator
Shaft breaker closed
Shaft generator not running
SHORE connection Shore breaker closed
3.4.4 [Source] voltage unbalance (ANSI 47)
Protection
IEC symbol (IEC60617) ANSI (IEEE C37.2) IEC 61850 Operate time
Voltage unbalance (voltage asymmetry) UUB> 47 - < 200 ms*
*Note: This operate time includes the minimum user-defined delay of 100 ms.
DESIGNER'S HANDBOOK 4189340911K UK Page 63 of 521