EasyManua.ls Logo

Deif PPM 300 - Pt1000

Deif PPM 300
521 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sensor value (Ω) Function input [°C]
264.220 450
281.028 500
297.548 550
313.780 600
329.725 650
345.382 700
360.751 750
375.832 800
390.626 850
405.132 900
419.350 950
433.280 1000
20.4.4 Pt1000
Table 20.12
Pt1000 analogue input curve (resistance to temperature)
Sensor value (Ω) Function input [°C]
803.068 -50
842.710 -40
882.218 -30
921.600 -20
960.859 -10
1000.000 0
1039.025 10
1077.936 20
1116.731 30
1155.411 40
1193.976 50
1232.426 60
1270.761 70
1308.981 80
1347.085 90
1385.075 100
1422.949 110
1460.709 120
1498.353 130
1535.882 140
1573.296 150
1610.595 160
1647.779 170
DESIGNER'S HANDBOOK 4189340911K UK Page 517 of 521