Deif PPM 300 - Source];[Busbar] L# Wire Break

Deif PPM 300
521 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configure > Parameters > [Busbar] > AC setup > Multiple phase wire break
Table 3.66 Default parameters
Parameter Range Default
Enable Not enabled, Enabled Enabled
Latch Not enabled, Enabled Enabled
Alarm action Warning
3.7.2 [Source]/[Busbar] L# wire break
Controller types: GENSET, SHAFT generator, SHORE connection and BUS TIE breaker controllers
These alarms alert the operator to a measurement failure on a phase:
[Source] L1 wire break
[Source] L2 wire break
[Source] L3 wire break
[Busbar] L1 wire break
[Busbar] L2 wire break
[Busbar] L3 wire break
The controller only activates the alarm when all of these conditions are met:
The generator breaker is closed
Voltage is detected by one set of ACM voltage measurements
No voltage is detected on one of the phases for the other set of ACM voltage
measurements
0
1
Time
Busbar
L1
Wire break
L1 L2 L3
Generator
voltage
L1 L2 L3
Busbar
voltage
Parameters
Configure the [Source] parameters under Configure > Parameters > [Source] > AC setup > L# wire break, where # is 1, 2 or 3.
Configure the [Busbar] parameters under Configure > Parameters > [Busbar] > AC setup > L# wire break, where # is 1, 2 or 3.
Table 3.67
Default parameters
Parameter Range Default
Enable Not enabled, Enabled Enabled
Latch Not enabled, Enabled Enabled
Alarm action Warning
3.8 ACM module general protections
3.8.1 ACM 1 protections not running
This alarm communicates that the configuration data for protections and measurements are not correct in the controller alternating
current module (ACM).
DESIGNER'S HANDBOOK 4189340911K UK Page 88 of 521