Alarms
Maximum parallel time
SG-DG maximum parallel time
SG-SG maximum parallel time
Power management
Heavy consumer feedback timeout (1 alarm for each heavy consumer)
Heavy consumer reservation not possible (1 alarm for each heavy consumer)
Regulation
• GOV regulation error
• GOV regulation mode not selected
• GOV stand-alone configuration error**
• P load sharing failure
• AVR regulation error
• AVR regulation mode not selected
• AVR stand-alone configuration error**
• Q load sharing failure
Non-essential load (NEL)
• Up to 3 non-essential loads per controller
• Can connect each controller to the same 3 non-essential load breakers
NEL # over-current (1 alarm for each non-essential load)
NEL # under-frequency (1 alarm for each non-essential load)
NEL # overload 1 and 2 (2 alarms for each non-essential load)
NEL # reactive overload (1 alarm for each non-essential load)
Other Trip AVR output not configured
*Note: The default SHAFT generator controller does not include EIM3.1 (required for this alarm).
**Note: Only in GAM3.2.
10.5.2 Alarm actions
The controller has the following alarm actions:
• Warning
• Block
• PMS-controlled open breaker
• Trip shaft breaker
• Trip AVR*
• Trip generator breaker + AVR*
• Trip generator breaker + AVR + stop engine*
• Trip generator breaker + AVR + shutdown engine*
*Note: These alarm actions are only available if the Trip AVR digital output is configured.
10.5.3 Inhibits
The SHAFT generator controller includes the following inhibits:
Table 10.16
SHAFT generator controller inhibits
Inhibit Disables the alarm when ...
Engine running Running detection is ON.
Engine not running Running detection is OFF.