Table 13.4 Changeover relay, normally de-energised coil
Function
Coil
NC circuit
NO circuit
NCNO
(1)
(2)
(4)
(3)
1. Function: The digital output function assigned to the terminals. The controller
software activates the function. For example: Breakers > [Breaker] >
Command > [*B] Close.
2. Coil: The controller energises the relay coil when the function is activated.
3. Normally open circuit: The normally open circuit closes when the coil is
energised.
4. Normally closed circuit: The normally closed circuit opens when the coil is
energised.
Table 13.5
Changeover relay, normally energised coil
NCNO
Function
Coil
NC circuit
NO circuit
(1)
(2)
(4)
(3)
1. Function: The digital output function assigned to the terminals. The controller
software activates the function. For example: Breakers > [Breaker] >
Command > [*B] Close.
2. Coil: The controller de-energises the relay coil when the function is activated.
3. Normally open circuit: The normally open circuit opens when the coil is de-
energised.
4. Normally closed circuit: The normally closed circuit closes when the coil is
de-energised.
13.2.4 Digital input characteristics and configuration
Symbol
Hardware modules
IOM3.1
IOM3.4
EIM3.1
GAM3.2
The controller can use digital inputs for many purposes. Examples: Command buttons, breaker feedback, and alarms.