Function I/O Type Details
V
new
= V
nom
+ (V
nom
× Voltage offset)
Regulators > AVR > Reactive
power set point [%]
Analogue
input
% of nominal
reactive
power
When configured, the controller receives the reactive power set
point from this analogue input. The internal controller value for
the reactive power set point is ignored.
Regulators > AVR > Cos phi set
point
Analogue
input
-
When configured, the controller receives the cos phi set point
from this analogue input. The internal controller value for the
cos phi set point is ignored.
Regulators > GOV > External
set points > Activate external f
offset
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > GOV general configuration >
External offset > Frequency offset enable to Enabled.
Regulators > GOV > External
set points > Deactivate external
f offset
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > GOV general configuration >
External offset > Frequency offset enable to Not enabled.
Regulators > GOV > External
set points > Activate external P
set point
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > GOV general configuration >
External offset > P set point enable to Enabled.
Regulators > GOV > External
set points > Deactivate external
P set point
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > GOV general configuration >
External offset > P set point enable to Not enabled.
Regulators > AVR > External
set points > Activate external V
offset
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > AVR general configuration >
External offset > Voltage offset enable to Enabled.
Regulators > AVR > External
set points > Deactivate external
V offset
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > AVR general configuration >
External offset > Voltage offset enable to Not enabled.
Regulators > AVR > External
set points > Activate external Q
set point
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > AVR general configuration >
External offset > Q set point enable to Enabled.
Regulators > AVR > External
set points > Deactivate external
Q set point
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > AVR general configuration >
External offset > Q set point enable to Not enabled.
Regulators > AVR > External
set points > Activate external
cos phi set point
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > AVR general configuration >
External offset > Cos phi set point enable to Enabled.
Regulators > AVR > External
set points > Deactivate external
cos phi set point
Digital input Pulse
When activated, the controller changes Configure >
Parameters > Regulators > AVR general configuration >
External offset > Cos phi set point enable to Not enabled.
Governor parameters
You can configure the governor common settings under Configure > Parameters > Regulators > GOV general configuration.
INFO
To see these parameters, you must assign a governor output function.
External offset
These parameters allow analogue inputs to determine the genset's frequency or power set point.
Parameter
Range Default Notes
Frequency offset
enable
Not enabled
Enabled
Not
enabled
Not enabled: The controller ignores the Frequency offset [%] analogue
input and Modbus input.
DESIGNER'S HANDBOOK 4189340911K UK Page 186 of 521