Wiring example
Figure 6.4 Example of analogue output wiring for governor regulation
Regulators > GOV > GOV output [%]
G
Figure 6.5 Example of pulse width modulation analogue output wiring for governor regulation
Regulators > GOV > GOV output [%]
G
Inputs and Outputs
You must assign the governor regulation analogue output under Configure > Input/output. Select the hardware module, then select
an analogue output to configure.
Table 6.6
Governor regulation analogue output
Function I/O Units Details
Regulators > GOV > Command
> Reset GOV to offset
Digital input Pulse
When the operator activates this digital input, the analogue
output is reset to the GOV output offset value.
Regulators > GOV > GOV
output [%]
Analogue
output
-100 to 100 %
The controller adjusts this output to regulate the governor.
DEIF recommends that you use the full range of the output, that
is from -100 % to 100 %, when you configure the output.
INFO
The setup and parameters for governor regulation using pulse width modulation (PWM) is exactly the same as for an
analogue output.
DESIGNER'S HANDBOOK 4189340911K UK Page 193 of 521