See the Appendix: Pre-configured curves for the curve details.
Output for a switchboard instrument
Output Generator power example
The customer has a 1 MW genset, and wants to display the power from the genset on the switchboard. He uses a DEIF
DQ-96x with a scale from -100 to 1500 kW.
The designer creates the following wiring for a Generator > Power (P) > Generator | Total [kW] analogue output:
-
+
The designer configures a customised function curve with an output of 4 mA for -100 kW, and 20 mA for 1500 kW.
DESIGNER'S HANDBOOK 4189340911K UK Page 422 of 521