EasyManua.ls Logo

Deif PPM 300 - Page 45

Deif PPM 300
521 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
You must set these parameters if you do not want the AC measurements that the controller uses for the alarms to be phase-to-
phase. These parameters determines whether the controller uses phase-to-phase or phase-to-neutral voltages.
Measurements from the neutral line can be present for phase-to-phase measurements.
Parameter Range Default Notes
AC setup
Phase-
phase
Phase-
neutral
Phase-
phase
Phase-phase: The controller uses the phase-to-phase voltages for the alarms (that is,
L1-L2, L2-L3, and L3-L1). See the Installation instructions for a wiring examples
for a phase-to-phase AC configuration.
Phase-neutral: The controller uses the phase-to-neutral voltages for the alarms (that is,
L1-N, L2-N, and L3-N). Measurements from the neutral line must be present in a phase-
to-neutral system.
If you select Single-phase L1 (or L2 or L3), you must also select Phase-neutral.
More information
See Wiring for examples controller functions, AC measurement wiring, System AC configuration in the Installation
instructions for an example of wiring required for the phase-to-neutral voltage measurements.
INFO
This parameter does not affect the nominal voltages. The nominal voltages are always phase-to-phase voltages.
Phase direction: AC phase rotation
Configure this parameter under Configure > Parameters > [Source] > AC setup > Phase direction.
You must set this parameter if the AC phase rotation is not L1-L2-L3.
This parameter must be the same in all the controllers in the system.
Parameter
Range Default Notes
AC phase
rotation
L1-L2-L3
L1-L3-L2
L1-L2-L3
L1-L2-L3: The global standard phase rotation is L1-L2-L3. Using an alternative
wiring can lead to confusion, fatal accidents and serious damage to equipment.
L1
L2 L3
Voltage
[V]
Time [s]
L1-L3-L2: DEIF does not recommend that you wire the system L1-L3-L2, due to
the potential for confusion. However, this parameter allows the controller to
function correctly even though the generator is wired L1-L3-L2.
DESIGNER'S HANDBOOK 4189340911K UK Page 45 of 521

Table of Contents

Other manuals for Deif PPM 300

Related product manuals