EasyManua.ls Logo

Deif SGC 120 - Page 37

Deif SGC 120
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engine Control Unit (ECU)
Parameter Range Default Description
Engine Type
None
Conventional
Generic J1939
Scania
Volvo
Iveco
Deutz - EMR
MTU
KUBOTA
Weichai
Hatz
PERKINS ADEM4
Yuchai YCGCU ECU
Cummins
Yuchai Bosch
Conventional Select the engine type.
Measurements from the ECU
Lube Oil Pressure
Enable
Disable
Not enabled Read and monitor the lube oil pressure.
Coolant Temperature
Enable
Disable
Not enabled Read and monitor the coolant temperature.
Engine Speed
Enable
Disable
Not enabled Read and monitor the engine speed.
Running Hours
Enable
Disable
Not enabled Read and monitor the engine running hours.
Battery Voltage
Enable
Disable
Not enabled Read and monitor the battery voltage.
Controls To ECU
Speed
Enable
Disable
Not enabled
If this is enabled, the controller sends the
requested engine speed to the ECU.
Engine Requested
Speed
500 to 4000 500
Start/Stop
Enable
Disable
Not enabled
If this parameter is enabled, the controller
sends the start/stop commands to the ECU.
Preheat
Enable
Disable
Not enabled
If this parameter is enabled, the controller
preheats the engine even if you have not
configured an output for preheat.
Engine Frequency - 500 Target speed of the ECU.
Engine Gain 0 to 10 5 Engine gain for Cummins engines.
ECU Communication Failure
Action
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for ECU communication
failure.
Activation
Never
From Engine Start
From Monitoring On
Always
While Fuel Relay ON
Never
Configure when the controller monitors the ECU
communication.
User manual 4189341340A EN Page 37 of 76