Parameter Range Default Description
Activation Delay 1 to 60 s 1 s
If there is a communication failure when the
delay timer expires, the action for ECU
communication failure is activated.
Communication Setup
SGC Source Address 0 to 253 3 Source address for the SGC.
ECU Source Address 0 to 253 0 Source address for the ECU.
ECU Diagnostic Lamps  Red, Malfunction, Protect)
Action
None
Notification
Warning
Electrical Trip
Shutdown
None
Configure the action for the ECU diagnostics
lamps.
Activation
Never
From Engine Start
From Monitoring On
Always
Never
Configure when the controller monitors the
diagnostics lamps.
Activation Delay 0 to 60 s 0 s
If there is a failure when the delay timer expires,
the action for the ECU diagnostics lamps is
activated.
Engine Coolant Temperature
Parameter
Range Default Description
Shutdown
Enable
Disable
Not enabled
If this parameter is enabled, the controller shuts
down the engine when the temperature is more
than the shutdown set point 
Threshold).
Shutdown Threshold 27 to 300 °C 27 °C
If the engine temperature is more than this set
point, the controller shuts down the engine.
Warning
Enable
Disable
Not enabled
If this parameter is enabled, the controller
activates a warning alarm when the
temperature is more than the warning set point
 Threshold).
Warning Threshold 25 to 298 °C 25 °C
If the engine temperature is more than this set
point, the controller activates a warning alarm.
Temp. Threshold Type
Greater Than
Threshold
Less Than Threshold
Greater Than
Threshold
Configure if the controller activates a shutdown
and/or a warning when the monitored value is
less than or more than the set points.
Lube Oil Pressure (LOP)
Parameter
Range Default Description
Low Level Shutdown
Enable
Disable
Not enabled
If this parameter is enabled, the controller shuts
down the engine when the lube oil pressure is
less than the shutdown set point 
Threshold).
Shutdown Threshold 0.0 to 9.8 Bar 2 Bar
If the lube oil pressure is less than this set
point, the controller shuts down the engine.
Low Level Warning
Enable
Disable
Not enabled
If this parameter is enabled, the controller
activates a warning alarm when the lube oil
User manual 4189341340A EN Page 38 of 76