No. Source Description
• Mains monitoring is enabled and there is a mains failure. The input is
deactivated. The is still a mains failure and the mains breaker opens.
15 V-belt broken switch
When this input is activated an alarm is shown on the display. You can
configure the alarm type.
16 Neutral SW signal This input is for CAN bus.
17 Regeneration SW inhibit signal This input is for CAN bus.
18 Mains contactor latched
When this input is activated, the mains breaker closes and the genset
breaker opens.
19 Gen contactor latched
When this input is activated, the genset breaker closes and the mains
breaker opens.
20 Idle mode enable You can activate idle mode with this input.
21 Alternate nominal switch
If this input is activated, the default nominal settings switch to the
alternative nominal settings.
9.2 Digital outputs
No. Output source Description
1 Disable The output is not used.
2 Sounder alarm
This output is high when an alarm is generated. The output is active for the
duration of the alarm.
3 Battery over volt
This output is activated when there is an active alarm for battery over-
voltage.
4 Battery under volt
This output is activated when there is an active alarm for battery under-
voltage.
5 Charge alt shutdown
This output is activated when there is an active shutdown alarm for charge
failure.
6 Charge alt warning
This output is activated when there is an active warning alarm for charge
failure.
7 Close gen contactor
This output is activated when the digital input for close genset/open mains
is activated in manual mode.
8 Close mains contactor
This output is activated when the digital input for close mains/open genset
is activated in manual mode.
9 Mains failure This output is activated when there is a mains failure.
10 Common alarm This output is activated when one of the alarm types is activated.
11 Common electrical trip This output is activated when there is an active electrical trip alarm.
12 Common shutdown This output is activated when there is an active shutdown alarm.
13 Common warning This output is activated when there is an active warning alarm.
14 Cooling down
This output is activated when the cooldown period of the genset is
initiated. The output is activate for the duration of the period.
15 Dig In A This output is activated when digital input A is activated.
16 Dig In B This output is activated when digital input B is activated.
17 Dig In C This output is activated when digital input C is activated.
18 Dig In D This output is activated when digital input D is activated.
19 Dig In E This output is activated when digital input E is activated.