No. Output source Description
20 Dig In F This output is activated when digital input F is activated.
21 Dig In G This output is activated when digital input G is activated.
22 Dig In H This output is activated when digital input H is activated.
23 Dig In I This output is activated when digital input I is activated.
24 Emergency stop This output is activated when the emergency stop is activated.
25 Stop solenoid This output is activated when the stop solenoid output is high.
26 Fail to start This output is activated when the fail to start alarm is activated.
27 Fail to stop This output is activated when the fail to stop alarm is activated.
28 Fuel relay This output is activate when the fuel relay is active.
29 Gen available This output is activated when the timer for the warm-up delay expires.
30 L1 phase OV shutdown
This output is activated when the over-voltage shutdown alarm for phase L1
is activated.
31 L1 phase UV shutdown
This output is activated when the under-voltage shutdown alarm for phase
L1 is activated.
32 L2 phase OV shutdown
This output is activated when the over-voltage shutdown alarm for phase
L2 is activated.
33 L2 phase UV shutdown
This output is activated when the under-voltage shutdown alarm for phase
L2 is activated.
34 L3 phase OV shutdown
This output is activated when the over-voltage shutdown alarm for phase
L3 is activated.
35 L3 Phase UV Shutdown
This output is activated when the under-voltage shutdown alarm for phase
L3 is activated.
36 Gen over current
This output is activated when the controller shuts down the genset
because of over-current.
37 High engine coolant temp
This output is activated when the alarm for high engine temperature is
activated.
38 Low fuel LVL This output is activated when the low fuel alarm is activated.
39 Low LOP This output is activated when the low LOP alarm is activated.
40 Mains high volt
This output is activated when the mains voltage is more than the
configured value.
41 Mains low volt
This output is activated when the mains voltage is less than the configured
value.
42 Oil pressure open circuit
This output is activated when the alarm for oil pressure (open circuit) is
activated.
43 Open gen contactor
This output is activated when:
• The close mains/open genset input is activated or
• When the load is transferred to the mains in AMF mode.
44 Open mains contactor
This output is activated when:
• The close genset/open mains input is activated or
• When the load is transferred to the genset.
45 Over freq shutdown
This output is activated when the shutdown alarm for over-frequency is
activated.
46 Over speed shutdown
This output is activated when the shutdown alarm for overspeed is
activated.
User manual 4189341340A EN Page 73 of 76