Power Status = ON
===============================================================================
Session Information
===============================================================================
Type User IP Address Login Date/Time
SSH root 10.9.72.252 11/28/2007 23:40:53
KVM root 169.254.31.30 11/28/2007 18:44:51
===============================================================================
Sensor Information
===============================================================================
<
senType> <Num> <sensorName> <status> <reading> <units> <lc>
<uc>
FanSpeed 1 Fan-1 OK 14495 rpm 7250 14500
FanSpeed 2 Fan-2 OK 14505 rpm 7250 14500
FanSpeed 3 Fan-3 OK 4839 rpm 2344 14500
FanSpeed 4 Fan-4 OK 14527 rpm 7250 14500
FanSpeed 5 Fan-5 OK 14505 rpm 7250 14500
FanSpeed 6 Fan-6 OK 4835 rpm 2344 14500
FanSpeed 7 Fan-7 OK 14521 rpm 7250 14500
FanSpeed 8 Fan-8 Not OK 1 rpm 7250 14500
FanSpeed 9 Fan-9 OK 4826 rpm 2344 14500
<
senType> <Num> <sensorName> <status> <reading> <units> <lc>
<uc>
Temp 1 Ambient_Temp OK 21 celcius N/A 40
<
senType> <Num> <sensorName> <status> <AC-OK status>
PWR 1 PS-1 Online OK
PWR 2 PS-2 Online OK
PWR 3 PS-3 Online OK
PWR 4 PS-4 Slot Empty N/A
PWR 5 PS-5 Failed OK
PWR 6 PS-6 Slot Empty N/A
racreset
Description
Resets CMC. The reset event is logged in the hardware (SEL) and CMC (RAC) logs.
To run this subcommand, you must have the Chassis Administrator privilege.
NOTE: After you run the racreset subcommand, CMC may require up to two minutes to return to a
usable state.
NOTE: There is a 100 percent fan request when the command is run against the servers.
Synopsis
racadm racreset [-m <module> [-f]]
Input
-m — The values must be one of the following:
server–<n> — where n=1–16
server–<nx> — where n=1–8; x = a, b, c, d (lower case)
NOTE:
Multiple modules may be specied, such as -m <module1> -m <module 2>.
-f option is used to force the reset and is available only with an -m option.