Chapter 6 Applied Instructions
6-95
conversion is that the value converted in the binary integer. However, the instruction FBIN can
be used to convert the floating-point number into the single-precision floating-point number.
2. When X0.0 is ON, K314 and K-2 are moved to D0 and D1 respectively, and combine into the
decimal floating-point number (3.14=314×10
-2
).
Additional remark:
If the real number of the decimal floating-point number in the operand S is not within the range
between -9,999 and +9,999, or if the exponent of the decimal floating-point number in the operand S
is not within the range between -41 and +35, the instruction is not executed, SM0 is ON, and the
error code in SR0 is 16#2013.