AH500 Programming Manual
7-28
7.1.9
AH10PFBM-5A
Error
code
Description
LED indicator status
CPU
MODULE
BUS
FAULT
RUN SYS DP
16#A001
The master is not set.
The red
light
blinks.
The green
light is
ON.
The green
light is
ON.
The green
light
blinks.
16#A003
The master station enters the test
mode.
The red
light
blinks.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A005
A timeout occurs when chips
inside the master station
communicate.
The red
light
blinks.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A00B
A timeout occurs when
AH10PFBM-5A exchanges data
exchange with a PLC.
The red
light
blinks.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A402
The PLC does not assign the I/O
mapping area to the master.
The red
light is
ON.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A404
Master initializing error
The red
light is
ON.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A406
Internal storage unit error
The red
light is
ON.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A407
Data exchange unit error
The red
light is
ON.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A408
Master serial number detection
error
The red
light is
ON.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
16#A4E2
The master detects that all the
slaves are offline.
The red
light is
ON.
OFF
The green
light is
ON.
The red
light is ON.
The master detects that some of
the slaves are offline.
The red
light is
ON.
OFF
The green
light is
ON.
The red
light
blinks.
16#A4E6
The master detects that an error
occurs in the module connected
to AHRTU-PFBS-5A.
The red
light is
ON.
The green
light is
ON.
The green
light is
ON.
The green
light is
ON.
7.1.10
AH10PFBS-5A
Error
code
Description
LED indicator status
CPU
MODULE
BUS FAULT RUN NET
16#A4F0
The node address of
AH10PFBS-5A exceeds the valid
range.
The red light is
ON.
The green light
is ON.
The green light
is ON.
16#A4F1
Internal hardware error
The red light is
ON.
The green light
is ON.
The green light
is ON.
16#A4F2
Parameter error
The red light is
ON.
The green light
is ON.
The green light
is ON.

Table of Contents