Chapter 6 Applied Instructions
6-147
set to ON.
(b) If the external 24 V voltage of the first local extension backplane is abnormal, bit 1 in SR731
will be set to ON.
4. The external interrupts (I40~I251)
If a peripheral device, e.g. a special I/O module, sends an interrupt request, the PLC will
execute the specific interrupt task.
5. The timed interrupts (I252~I255)
Timed interrupt 0 (I252): The default value is 100 milliseconds (1~1000 milliseconds).
Timed interrupt 1 (I253): The default value is 40 milliseconds (1~1000 milliseconds).
Timed interrupt 2 (I254): The default value is 20 milliseconds (1~1000 milliseconds).
Timed interrupt 3 (I255): The default value is 10 milliseconds (1~1000 milliseconds).
The timed interrupt task is executed every specific period of time. For example, the timed
interrupt task is executed every 10 milliseconds.
The priority order is a follows.
Interrupt number
Description
Priority order
I0
I/O interrupt 0
1
I1
I/O interrupt 1
2
I2
I/O interrupt 2
3
I3
I/O interrupt 3
4
I4
I/O interrupt 4
5
I5
I/O interrupt 5
6
I6
I/O interrupt 6
7
I7
I/O interrupt 7
8
I8
I/O interrupt 8
9
I9
I/O interrupt 9
10
I10
I/O interrupt 10
11
I11
I/O interrupt 11
12
I12
I/O interrupt 12
13
I13
I/O interrupt 13
14
I14
I/O interrupt 14
15
I15
I/O interrupt 15
16
I16
I/O interrupt 16
17
I17
I/O interrupt 17
18
I18
I/O interrupt 18
19
I19
I/O interrupt 19
20
I20
I/O interrupt 20
21
I21
I/O interrupt 21
22
I22
I/O interrupt 22
23
I23
I/O interrupt 23
24
I24
I/O interrupt 24
25
I25
I/O interrupt 25
26
I26
I/O interrupt 26
27
I27
I/O interrupt 27
28
I28
I/O interrupt 28
29
I29
I/O interrupt 29
30
I30
I/O interrupt 30
31
I31
I/O interrupt 31
32
I32
Communication interrupt
(COM1)
33