Chapter 6 Applied Instructions
6-227
6.11.2 Explanation of Timer and Counter Instructions
API
Instruction code Operand
Function
1000 RST
D
Resetting the contact or
clearing the register
Device
X Y M S T C HC D L SM SR E PR K 16# “$ DF
D
Pulse instruction
16-bit instruction (3 steps)
32-bit instruction
AH500
Symbol:
D
Device which is reset Bit/Word
Explanation:
1. When the instruction RST is driven, the action of the device specified is as follows.
Device
status
Bit
The coil and the contact are set to OFF.
T, C, and HC
The timer and the counter are reset to 0, and the coil and the contact are set
to OFF.
Word
The value is cleared to 0.
2. If the instruction RST is not executed, the status of the device specified is unchanged.
3. The instruction supports the direct output.
Example:
When X0.0 is ON, Y0.5 is set to OFF.