Chapter 6 Applied Instructions
6-229
API Instruction code Operand
Function
1002 TMRH
S
1
, S
2
16-bit timer
Device
X Y M S T C HC D L SM SR E PR K 16# “$ DF
S
1
S
2
Pulse instruction
16-bit instruction (5 steps)
32-bit instruction
AH500
Symbol:
S
1
Timer number Word
S
2
Setting value of the timer Word
Explanation:
1. The timer used in the instruction TMR takes 100 milliseconds as the timing unit, and the timer
used in the instruction TMRH takes 1 millisecond as the timing unit.
2. The timers for the subroutines exclusive use are T1920~T2047.
3. The values of the timers used in TMR and TMRH should be within the range between 0 and
32767.
4. If the same timer is used repeatedly in the program, including in the different instructions TMR
and TMRH, the setting value is the one that the value of the timer matches first.
5. As long as users add the letter S in front of the device T, the timer used in the instruction TMR
becomes the accumulative timer. When the conditional contact is OFF, the accumulative timer
value is not reset. When the conditional contact is ON, the timer counts from the current value.
6. If the same timer is used repeatedly in the program, it is OFF when one of the conditional
contacts is OFF.
7. If the same timer is used repeatedly as the timer for the subroutines exclusive use and the
accumulative timer in the program, it is OFF when one of the conditional contacts is OFF.
8. When the timer is switched from ON to OFF and the conditional contact is ON, the timer is
reset and counts again.
9. When the instruction TMR is executed, the specified timer coil is ON and the timer begins to
count. As the value of the timer matches the setting value, the state of the contact is as follows.
Normally open (NO) contact
ON
Normally closed (NC) contact
OFF
Example 1:
When X0.0 is ON, the setting value 50 is loaded to the timer T0. When the value of T0 matches 50,
the contact of T0 is ON.